Where to start
- From a safe position, record fan state, water flow, wind and whether droplets appear at discharge, air inlets or the basin. A visible plume can be condensation. Wet surfaces near the basin can also come from splash or overflow.
- After safe isolation, check the rotating distributor and spray holes for blockage, misalignment or abnormal wear. Check eliminator coverage, direction and gaps where air can bypass it, following the tower model’s arrangement.
- Check basin water level, overflow, make-up valve and leakage. Record make-up and blowdown and review cycles of concentration when evaluating total water use. Use OEM data or a suitable drift test for the drift rate.
Tower shape helps locate inspection points. Actual drift depends on equipment, condition and operating point. With concentration control, blowdown may change when drift changes.